Power Protection - Bypass Transfer Switch - ZBTS
Power Protection We bring good things to life.
 
 
Give Us Feedback
Products
·Fusegear
·Switchgear
·Controlgear
·Circuit Breakers
·Busbar Systems
·Residential
·Transfer Switches
·Panel Accessories
·Capacitors
·UPS
Switchboards
·Motor Control Centers
·Power Control Centers
·Marine Switchboards
GE Grässlin
Projects and Services
Commercial Support
About GE Power Controls
TDC
Career Opportunities

      

 
Bypass Transfer Switch - ZBTS
Power Protection India | Products | Transfer Switches | Bypass Transfer Switch - ZBTS
 

    Other Range of Bypass Switches   ZBTSD

 

In critical applications such as those of hospitals and airports, power cannot be interrupted for maintenance of automatic transfer switches (ATSs). In such circumstances, a bypass-isolation switch is essential and is often required by code.

GE Zenith Controls ZBTS Series Bypass-Isolation Transfer Switches are the solution when interruption of power during service or testing is not acceptable.

Consisting of two major modules-the ATS and bypass-isolation switch-the ZBTS Series incorporates the rugged construction of all our ZTS Series switches with a quick-make/quick-break manual load transfer handle and our control/interlock system, which consists of both mechanical and electrical interlocks.

The bypass uses normal failure sensing and a time delay to start the engine automatically if a failure occurs when the ATS has been removed for service, which can be done without disturbing the load.


Electrical Ratings

  • Ratings 100 to 4000 amperes
  • 2, 3 or 4 poles
  • Open type, NEMA 1, 3R, 4, 4X and 12
  • Available with ZTS, ZTSD and ZTSCT Series Transfer Switch
  • Bypass and transfer switch have identical ratings
  • Suitable for emergency and standby applications on all classes of load, 100% tungsten rated through 400 amps
  • UL 1008 listed at 480 VAC
  • CSA C22.2 No. 178 certified at 600 VAC
  • IEC 947-6-1 listed at 480 VAC


Performance Features

  • Load is not interrupted during bypass operation
  • High close-in and withstand capability
  • Temperature rise test per UL 1008 conducted after overload and endurance tests in unventilated enclosure?2014exceeds UL requirements
  • Available in ZBTS (utility-generator), ZBTSU (utility-utility), ZBTSG (generator-generator) and ZBTSM (manual) configurations; models include standard, delayed and closed transition


Design and Construction Features

  • Transfer switch is located on a draw-out mechanism to facilitate maintenance
  • Emergency power systems can be electrically tested without disturbing the load
  • Power cables do not have to be disconnected to remove transfer switch
  • Bypass to any available source with ATS removed
  • Engine start circuit maintained during bypass operation; normal power failure causes engine start contact closure even with the ATS removed
  • Diagnostic lights and detailed instructions for simple step-by-step operation
  • Mechanical and electrical interlocks ensure proper sequence of operation
  • Bypass switch contacts are closed only during the bypass-isolation operation
  • Silverplated copper bus interconnection of the transfer and bypass switches on all sizes
 

zbtss.jpg
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Guide Specification
Dimensions/Weights
Withstand Ratings
Instruction Manuals
Sequence of operation
Product Brochure

Standard Drawings