DC EP100UC
- Specialised MCB for DC applications
- Ratings 0.5A, 1A, 2A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A
- Type B and C tripping characteristics (details available on request)
- 6kA short circuit capacity (IEC 898)
- 1P (250V DC), 2P (500V DC), 4P (880V DC)
- Current limiting operation under fault conditions
- 18mm modular width per pole
- IP20 finger proof terminals
- Safety terminals ensure that incorrect connection is not possible
- Terminal capacity up to 35mm²
- High torque terminals up to 4.5Nm
- Circuit indicator window allowing clear labeling of circuits
- Suitable for DIN rail mounting in OEM / panel builder enclosures
- Suitable for installation in consumer units, design units and MCB distribution boards
- Toggle is padlockable in "ON" or "OFF" position
- Wide range of multi-functional accessories
MCBs for photovoltaic applications
Application as loadbreak disconnector
The first solution for the growing market of
solar electric power.
- Compact design
- High voltage 880V upto 63A
- Safetylock with padlocking bracket
- Add-on devices for remote signalisation and tripping
- Add-on motor driver Tele MP
| |
|
Series EP100UC
|
Series EP104UC
|
| Curve |
|
B |
B |
| Thermal setting In |
(A) |
6 - 63 |
10 - 63 |
| Rated voltage DC Un |
(V) |
500 |
880 |
| Maximum operating voltage DC |
(V) |
520 |
1000 |
| Minimum operating voltage DC |
(V) |
12 |
12 |
| As loadbreak disconnector |
|
yes |
yes |
| Rated insulation voltage Ui |
|
|
|
| Pollution degree 2 |
(V) |
500 |
1200 |
| Pollution degree 3 |
(V) |
440 |
1000 |
| Rated impulse withstand voltage Uimp |
(kV) |
6 |
6 |
| Dielectric rigidity |
(kV) |
2,5 |
2,5 |
| Mechanical/electrical endurance |
|
20000/1000 ops. |
|
Reconnection Relays and Surge Arresters also available for photovoltaic applications
|
|
 | Technical Product Search |
|
|
|
|
|