manual operated main switch must be provided for every mains circuit. It must be a switch-disconnector corresponding to utilization category AC23 (IEC 947-3) fulfi ls the following requirements:

  • Disconnecting the electrical equipment from the main
  • Visible contact indication or a disconnection function by construction (the handle is in the "OFF" position when all contacts are open)
  • If the main switch does not serve simultaneously as an emergency-stop switch, its handle should not be red. Black or grey handles are recommended
  • It should be lockable in the off-position (e.g. by padlock)
  • All active conductors are to be disconnected from the main
  • The breaking capacity should be sufficient. In order to break the current of the largest motor in a blocked state together with the sum of the operating currents of the remaining motors/loads
  • The handle of the main switch must be easily accessible and must lie between 0.6 and 1.9 m above the incomer level

Emergency-stop equipment

The main switch may fulfi l the function of an emergency-stop switch on certain machines.

The handles must be red on a yellow background.

The contacts of manual operated emergency-stop switch has to be opened by force.

 

 

Series ML - Main Switches

 

Technical Data

Main switches - According to IEC 947-3, EN 60947-3, DIN VDE 0660 part 107, UL and CSA
Series ML 1 ML 1 ML 2 ML 2 ML 3
Types 640 650 660 670 680
Rated uninterrupted current Iu open = Ith (A) 25406380125
  Ithe enclosed (A) 25325063100
Rated insulation voltage Ui (III/3) (V) 690690690690690
Rated impulse withstand voltage Uimp (III/3) (kV) 66666
Rated operational current Ie AC21 A(³) (A) 25406380125
Rated operational voltage Ue (V) 690690690690690
Frequency (Hz) 50/6050/6050/6050/6050/60
Making/breaking capacity
Utilization category AC3: 3 x 230V (kW) 5.57.51518.522
Motor switches for 3 x 400V (kW) 7.511223037
operational switching 3 x 690V (kW) 7.511223045
Utilization category AC23A(³) 3 x 230V (kW) 7.51118.52225
Motor switches 3 x 400V (kW) 111530(¹)37(²)45
(Main switches for machinery) 3 x 690V (kW) 111530(¹)37(²)45
Rated breaking category AC23 A(³) 3 x 230V (A) 260390630750870
  3 x 400V (A) 220300570700850
  3 x 690V (A) 130170330400490
Short-circuit capacity
Max. fuse rating gG (A) 50508080125
Rated conditional short-circuit current (kAeff) 1010---
Rated short-circuit making capacity Icm (kA) --2.12.13.4
Rated short-time withstand Icw (1s-current) (Aeff) 3004807659601500
Disconnect function up to (V) 690690690 690690
Terminal screws (Pozidriv) M4M4M5M5M6
Torque terminal screws (Nm) 2.52.5446
Cable cross section
Solid or multi-stranded (Cu) min. - max. (mm²) 1.5-101.5-102.5-352.5-356-70
Flexible with ferrule (DIN 46228) min. - max. (mm²) 1.5-61.5-61.5-251.5-256-50
General purpose 3-phase (A) 25406380125
  (V) 600600600600600
Motor 3-phase 240V (HP) 7.510152025
  480V (HP) 1020304050
  600V (HP) 1020304050
Motor 1-phase (2 pole) 120V (HP) 11,5346
  240V (HP) 237,51015
Cable cross section AWG-No 14-714-314-214-28-1/0

 

(1) 22 kW in enclosure

(2) 30 kW in enclosure

(3) ML2/ML3 according to EN 60947-3 category B

 